Specifications: 1412B
| Detection: |
Ionization |
|
| Wiring: |
4-wire |
|
| Operating Voltage: |
12 VDC (11.3-17.3 VDC) |
|
| Alarm Current: |
77mA |
|
| Standby Current: |
120 µA max. |
|
| Auxiliary Contact: |
Form A, C |
|
| Auxiliary Contact Ratings: |
2.0A @ 30 VAC/DC (Form A, C); 0.6A @ 110 VDC, 1.0A @ 125 VAC (Form C) |
|
| Temperature Range: |
32° to 120°F (0° to 49°C) |
|
| Humidity Range: |
10% to 93% RH, noncondensing |
|
| UL Listed Velocity Range: |
1200 fpm max. |
|
| Sensitivity: |
1.9% ± 0.6%/ft. nominal |
|
| Wiring Gauge: |
12-22 AWG, twisted pair recommended |
|
| Dimensions: |
3.12" (8.1cm) H x 5.5" (13.9cm) Dia. |
|
| Weight: |
0.7 lb. |
| |
|