Sprinkler Systems Monitoring Product Line

Waterflow DetectorsSupervisory SwitchesPressure Switches
Explosion ProofAlarm BellsAccessories

Sprinkler Systems Monitoring

Series:
WFD
Type:
Waterflow Detector
Model:
WFDTH
Description:
The WFDTH is a T-Tap waterflow detector for use with a 1" NPT connection, in residential sprinkler systems.

WFDTH
CSFM MEA UL

Specifications: WFDTH

Pipe Size: 1" NPT Connection

Pipe Schedule: 1", 1-1/4", 1-1/2" ferrous/brass threaded tees; 1", 1-1/4", 1-1/2", 2" copper sweat tees; 1" CPVC tees; 1-1/2" polybutylene tees

Conduit Entrances: Two openings for 1/2" conduit

UL Pressure Rating: 250 PSI

Triggering Threshold Bandwidth Flow Rate: 4-10 GPM

Maximum Surge: 18 FPS

Enclosure Rating: UL NEMA 3

Operating Temperature Range: 32°F to 120°F (0° to 49°C)

Warranty: 3 years

Contact Ratings: Two sets of SPDT (Form C); 10.0A @ 125/250VAC; 2.5A @ 24VDC

Overall Dimensions: 4.5"H x 3.55"W x 6.7"L (11.4cm x 9cm x 17cm)

Shipping Weight: 2.6 lbs.