Audible Visible Notification
- Model:
SPSRK
- Series:
- SpectrAlert Advance
- Type:
- Speaker Strobe
- Description:
- The SpectrAlert Advance SPSRK is a red, outdoor speaker strobe for wall installations with selectable strobe settings of 15, 15/75, 30, 75, 95, 110 and 115 cd.
Specifications: SPSRK
| Color: |
Red |
| Voltage: |
25 Volts or 70.7 Volts (nominal) |
| Candela: |
Selectable Candela (15, 15/75, 30, 75, 95, 100, 115 cd) |
| Operating Voltage Range: |
8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal) |
| Operating Voltage Range with MDL3: |
9 to 17.5 V (12V nominal) or 17 to 33 V (24 nominal) |
| DC Max. Operating Current - Strobe: |
(see Data Sheet for complete current draw information) |
| FWR Max. Operating Current - Strobe: |
(see Data Sheet for complete current draw information) |
| Power: |
¼, ½, 1, 2 watts |
| Wiring Gauge: |
12-18 AWG |
| Frequency Range: |
400 to 4000 Hz |
| Operating Temperature: |
–40°F to 151°F (–40°C to 66°C) |
| Dimensions: |
6.0"L x 5.0"W x 4.7"D (including lens and speaker) |
|