This Model Has Been Discontinued

Conventional Detection

Model:

1400

Series:
400 Series
Type:
Direct-Wire Smoke Detector
Description:
The 1400 is a 2-wire, ionization smoke detector.

Specifications: 1400

Detection: Ionization
Wiring: 2-wire
Operating Voltage: 12/24 VDC (8.5-35 VDC)
Alarm Current: Two-wire control panels must be current limited 100 mA or less
Standby Current: 120 µA max.
Auxiliary Contact: Form A, C
Auxiliary Contact Ratings: 2.0A @ 30 VAC/DC (Form A, C); 0.6A @ 110 VDC, 1.0A @ 125 VAC (Form C)
Operating Temperature Range: 32° to 120°F (0° to 49°C)
Operating Humidity Range: 10% to 93% RH, noncondensing
UL Listed Velocity Range: 1200 fpm max.
Sensitivity: 1.9% ± 0.6%/ft. nominal
Wiring Gauge: 12-22 AWG, twisted pair recommended
Dimensions: 3.12" (8.1cm) H x 5.5" (13.9cm) Dia.
Weight: 0.7 lb.