Conventional Detection
- Model:
2W-MOD2
- Type:
- Accessory
- Description:
- The 2W-MOD2 is a two-wire loop test and maintenance module for use with i3 Series detectors. (Replaces Model No. 2W-MOD)
Specifications: 2W-MOD2
| Operating Voltage: |
12/24V nom.; 8.5V min. power limited; 30V max. power limited |
| Maximum Ripple Voltage: |
30% of applied voltage (peak to peak) |
| Alarm Current: |
90mA max. |
| Standby Current: |
30mA max. |
| Alarm Contact Ratings: |
0.5A @ 36VDC, Resistive |
| Dimensions: |
4.5"H x 4.0" W x 1.25" D (114mm x 101mm x 32mm) |
| Weight: |
8 oz. (225 g) |
| Maximum Maintenance Current: |
53mA |
| Maintenance Contact Ratings: |
2A @ 30VDC, Resistive |
| Operating Temperature Range: |
14°F to 122°F (-10°C to 50°C) |
| Operating Humidity Range: |
0 to 95% RH non-condensing |
| Wire Connections: |
14-22 AWG |
| Mounting: |
4" square back box |
|