Conventional Detection

Model:

BEAM1224

Type:
Reflected Type Beam Smoke Detector
Description:
The BEAM1224 is a 4-wire, single-ended, reflected type beam smoke detector that includes an 8" reflector.

Specifications: BEAM1224

Detection: Infrared Beam
Wiring: 4-wire
Operating Voltage: 10.2 to 32 VDC
Alarm Current: 38.5mA max. avg.
Standby Current: 17mA max. @ 24 VDC
Trouble Current: 8.5mA max. @ 24 VDC
Temperature Range: -22°F to 131°F (-30°C to 55°C)
Humidity Range: 10% to 93% RH noncondensing
Range: 16 ft. to 328 ft. (5m to 100m)
Sensitivity: Level 1 - 25%; Level 2 - 30%; Level 3 - 40%; Level 4 - 50%; Acclimate Level 1 - 30-50%; Acclimate Level 2 - 40-50%
Dimensions: Detector: 10" H x 7.5" W x 3.3" D (254mm x 191mm x 84mm); Reflector, 16-230ft.: 7.9" H x 9.1" W (200mm x 230mm)