Intelligent Detection Product Line

Smoke DetectorsDuct Smoke DetectorsBeam Smoke DetectorsThermal
EclipseModulesBasesPinnacleMulti-CriteriaAccessories

Intelligent Detection

Model:

M500R

Series:
500
Type:
Intelligent Module
Description:
Relay Module

Specifications: M500R

Operating Temperature Range: 32°F to 120°F (0°C to 49°C)
Operating Humidity Range: 10% to 93% noncondensing
Dimensions: 4.25"W x 4.65"H x 1.1"D
Shipping Weight: 6.3 oz. (196 g)
Voltage Range: 15 - 32 VDC
Standby Current: 300 uA max. @ 24 VDC with comm.
Contact Relay Ratings: 2.0 A @ 25 VAC (PF=.35), non-coded
3.0 A @ 30 VDC resistive, non-coded
2.0 A @ 30 VDC resistive, coded
0.46 A @ 30 VDC (L/R=20ms), non-coded
0.7 A @ 70.7 VAC (PF=.35), non-coded
0.9 A @ 125 VDC resistive, non-coded
0.5 A @ 125 VAC (PF=.75), non-coded
0.3 A @ 125 VAC (PF=.35), non-coded
Communication Line Impedance: 40 Ohms
End-of-Line Resistance: 47 k ohms
LED Current: 5.5 mA