Sprinkler Systems Monitoring Product Line

Waterflow DetectorsSupervisory SwitchesPressure Switches
Explosion ProofAlarm BellsAccessories

Sprinkler Systems Monitoring

Model:

WFD60EXP

Series:
WFD
Type:
Explosion-proof Waterflow Detector
Description:
The WFD60EXP is an explosion-proof waterflow detector for use with 6" pipe.

Specifications: WFD60EXP

Pipe Size: 6"
Pipe Schedule: 10 through 40
Conduit Entrances: Two openings for 1/2" conduit
UL Pressure Rating: 450 PSI
Triggering Threshold Bandwidth Flow Rate: 4-10 GPM
Maximum Surge: 18 FPS
Enclosure Rating: UL NEMA 4
Operating Temperature Range: 32°F to 120°F (0° to 49°C)
Warranty: 3 years
Contact Ratings: Two sets of SPDT (Form C); 10.0A @ 125/250VAC; 2.5A @ 24VDC
Overall Dimensions: 6"H x 9"L x 6.5"W
Shipping Weight: 12.5 lbs.
Hazardous Location Classifications: Class I, Div 1, Groups B,C,D; Class II, Div 1, Groups E,F,G; Class III, Div 1