Sprinkler Systems Monitoring Product Line

Waterflow DetectorsSupervisory SwitchesPressure Switches
Explosion ProofAlarm BellsAccessories

Sprinkler Systems Monitoring

Model:

WFD80

Series:
WFD
Type:
Waterflow Detector
Description:
The WFD80 is a waterflow detector for use with 8" pipe.

Specifications: WFD80

Pipe Size: 8"
Pipe Schedule: 10 through 40
Conduit Entrances: 1/2" conduit: one open, one knock-out type
UL Pressure Rating: 450 PSI
Triggering Threshold Bandwidth Flow Rate: 4-10 GPM
Maximum Surge: 18 FPS
Enclosure Rating: UL NEMA 4
Operating Temperature Range: 32°F to 120°F (0° to 49°C)
Warranty: 3 years
Contact Ratings: Two sets of SPDT (Form C); 10.0A, 1/2HP @ 125/250VAC; 2.5A @ 6/12/24VDC
Overall Dimensions: 4.6"H x 10.8"W
Shipping Weight: 7.5 lbs.