Sprinkler Systems Monitoring
- Model:
WFD80E
- Series:
- WFDE
- Type:
- Waterflow Detector
- Description:
- The WFD80E is a waterflow detector for use with 200mm (8") pipe and approved by FM, LPC, VdS, and SSL.
Specifications: WFD80E
| Pipe Size: |
200 mm (8") |
| Compatible Pipe: |
(see table on data sheet) |
| Conduit Entrances: |
Two openings 22.2mm (.875 in) diameter; one open, one knock-out type |
| Triggering Threshold Bandwidth Flow Rate: |
LPC: 20-57 liters/min.; VdS: 30-57 liters/min. |
| Enclosure Rating: |
IP54 |
| Operating Temperature Range: |
0°C to 68°C (32°F to 155°F) |
| Warranty: |
3 years |
| Contact Ratings: |
Two sets of SPDT (Form C) |
| Shipping Weight: |
3.45 kg (7.70 lb.) |
|